Maintenance
34 313296J
Electrical Enclosure
1. Turn the main disconnect on the electrical control
panel door to the OFF position to disconnect power.
2. Open door of electrical enclosure.
3. Check for damaged or loose wires. Check connec-
tions from cable track.
Check Ground Fault Circuit Interrupter
1. With electrical enclosure door still open, switch main
disconnect (421) back on.
2. Press Test button on ground fault circuit interrupter
(419). The blue switch should flip to the middle or
opposite side.
NOTE: Do not perform this test while the system is
in operation.
3. Press blue switch back into place to reset breaker.
4. Switch main disconnect off.
Power is still connected to the power line filter (459)
even after the main disconnect is open. Avoid con-
tact with the power line filter.
F
IG
. 31: Inside View of Electrical Enclosure
421
459
419
Have a qualified electrician restore power to main
disconnect while electrical enclosure door is open.
F
IG
. 32: Ground Fault Circuit Interrupter
419